CR3750

3750 kVAR 5/15 kV Portable Reactive Load Bank

The CR3750 MV is ideal for tests requiring a power factor of 0.8 at 5 and 15 kV class voltages. The reactors are housed in an 20’ ISO Container equipped with a fused disconnect, forced ventilation, operator control station manual with metering, and a networked capable PLC with remote touch screen, in a small but rugged protective case. 

The CR3750 MV reactive load bank is designed to be used in parallel with the CR922 resistive load bank to achieve a 0.8 power factor load.

Rugged designed iron core reactors, utilizing features from all severe duty and transport applications. Temperature rating 130º C rises, with internal thermal monitoring on the center phase/core. A re-connectable tap board is integrated with each reactor. 

The CR3750 MV reactive load bank is available for rental and long term leasing exclusively from ComRent® International, LLC.

Product Specifications

VOLTAGES: 2400, 4160, (6 kV, 11 kV, 50 Hz), 12470, 13,200, 13,800 and 14,400. 

LOAD STEPS 5 kV CLASS: 4160 L-L 300, 600, 900, 1200 kVAR. 

LOAD STEPS 15 kV CLASS: 13,800 L-L 375, 750, 1125, 1500 kVAR. 

CONTROLS: Mounted on the load bank including main power ON-OFF, blower START-STOP push buttons, fan rotation switch, master load and individual load step ON-OFF toggle switches. Remote option also available. 

CONTROL & BLOWER POWER: 120 VAC, singlephase, 60 Hz, 30 amp external source twist-lock connection. 100’ twist-lock—bare end cords  provided.

METERING: Integrated Digital Power Meter to measure Volts, Amps, kVAR, and Frequency.

CONSTRUCTION: International Shipping Container ISO 20’. 

SAFETY FEATURES: Motor overload protection, overtemperature protection, and cooling air loss protection.